SG Series General Features
Aluminum reflectors designed to maximize radiant output
SG Typical Applications:
Manufacturing Plants
Warehouses
Auto Dealerships
Aircraft Hangars
Loading Docks
Fire Stations
Commercial Garages
Machine Shops
Tennis Courts
Maintenance Shops
Farm Buildings
Truck Service Areas
Not Recommended for Residential Use
SG Technical Specifications
Model
|
Gas Type
|
Input Btu/hr
|
No. of Burners
|
Minimum Mounting
Height (ft.) |
SG13-L
|
LP
|
130,000
|
4
|
17
|
SG Supply Requirements
Gas Type
|
Burner Pressure |
Supply Pressure (water column)
|
|
|
|
Minimum
|
Maximum
|
Propane Gas
|
10"
|
11"
|
14"
|
Direct Spark Ignition System. 120 VAC. 0.40 Amp. Includes 120/24 V Transformer.
1/2 NPT Female Gas Connection.
SG Clearances to Combustibles (In Inches)
Model
|
Mounted Horizontally
|
Mounted at 30° angle
|
|||||||
|
Sides
|
Ceiling
|
Below
|
w/Reflector |
Below
|
w/Reflector
Extension |
Front
|
w/Reflector
Extension |
Rear
|
SG13
|
49
|
65
|
137
|
191
|
137
|
191
|
65
|
91
|
49
|
** This unit is LP Gas**