SELECTION NOTE:
Given the proper liquid line size and connection type, the correct drier may be selected using the chart in the "Product Information/Specifications" document below. Choosing a unit size with sufficient water capacity to reduce moisture content of the system to a safe level should be considered.
INSTALLATION NOTE:
The 96-TD liquid line filter-drier may be installed in any position. Best results are achieved when located as close as possible to the inlet of the expansion device. If using a liquid line solenoid or moisture indicator, locate the filter-drier upstream. This will provide protection to the solenoid valve and allow the moisture indicator to measure the drier effectiveness. Install the drier in as cold a location as possible in the direction of the flow arrow on the unit.
Overview
This filter-drier is designed to offer complete protection for your refrigerant system. The 96-TD series removes moisture, acid and foreign materials in order to protect the compressor, solenoid valves, expansion valves, capillary tubes and other close tolerance parts of your refrigeration system.